TM 9-6115-669-13&P
Table 1-4 Control Signals Between Generator Sets 150 kW and PDU.
ControlCabinetAssembly,
Designation
OV (24-VDC system)
BATTLE SHORT (S21)
OV (excitation of K12)
OV
J9 Parallel
Operation,
Contact
A
B
C
D
+24V
E
Interlock loop
F
AC CIRCUIT INTERRUPTER ON
G
OV
H
PARALLEL OPERATION ON (S9)
J
BATTERY CHARGING CONTROL
OIL PRESSURE
K
OIL TEMP-CYLINDER HEAD
AIR FILTER
K
UNDER/OVER FREQUENCY
K
UNDER/OVER VOLTAGE
K
GENERATOR OVER TEMPERATURE
K
OVERLOAD
K
REVERSE POWER
K
+24V
L
LOW FUEL
M
Affects
EPP III, OV (24 VDC system)
ECS, BATTLE SHORT switch
ECS, EMERGENCY switch
Commercial Power Converter op-
eration
EPP III operation
2nd Gen Set 150kW, J9-G, N-O con-
tact K14
2nd Gen Set 150kW, J9-F, energizes
K20
2nd Gen Set 150kW, J9-J, energizes
K18
2nd Gen Set 150kW, J9-H, OV (24
VDC system)
ECS, fault message
ECS, fault message
ECS, fault message
ECS, fault message
ECS, fault message
ECS, fault message
ECS, fault message
ECS, ON message Gen Set 150kW
ECS, LOW FUEL message Gen Set
150kW
+24V
I
N
EPP III, +24V (24 VDC system)
+24V
Power distribution
Active power output
Cable shield
OV
Power distribution
Reactive power
Cable shield
P
R
S
T
U
X
Y
Z
2nd Gen Set 150kW, J9-U, N-C con-
tact K19
2nd Gen Set 150kW, J9-R, N4,10
2nd Gen Set 150kW, J9-S, N4,11
2nd Gen Set 150kW, J9-T, cable
shield
2nd Gen Set 150kW, J9-P, energizes
K19
2nd Gen Set 150kW, J9-Y, N2, E
2nd Gen Set 150kW, J9-X, N2, A
2nd Gen Set 150kW, J9-Z, cable
shield
1-34