TM 9-6115-669-13&P
2.6.4 Check fuel level.
NOTE
The MASTER SWITCH (9, figure 2-16) is a five position switch:
Position One
- Locked and Gen Set 150 kW will not run in this position.
Position Two
- Off with the key fully inserted (pushed in); Gen Set 150 kW
will run in this position but cannot be started.
Position Three - Off with the key in the half-way inserted position; this is
the NORMAL shut down position.
Position Four
- Switch is on with key fully inserted; this is the NORMAL
start and run position.
Position Five
- Switch is on with key inserted half way; this is the EMER-
GENCY shut down position.
a. Open flap (4). Set MASTER SWITCH (9) to ON position.
b.
Read FUEL LEVEL meter (6). If fuel level is insufficient, refuel engine.
c.
Set MASTER SWITCH (9) to OFF position.
NOTE
If the LOW FUEL lamp (5) lights up during operation, refuel. If
refueling is not performed in time, the fuel system will draw in air and
must be bled.
2.6.4.1 Refueling.
The Generator Set 150 kW tank has a capacity of 101.7 gallons (385 liters) of diesel fuel, including
reserve. It can be filled with the fuel pump, a fueling nozzle, or a canister.
WARNING
When refueling a generator set from an external source such
as a fuel tanker, the external source must be grounded to the
generator set fuel tank before refueling to prevent any
electrical discharge.
If metal to metal contact is not maintained during refueling,
a spark may result which could ignite fuel fumes. Make sure
the fuel nozzle stays in contact with the fuel tank. Ensure the
grounding point is an unpainted metal surface.
The fuel in this Generator Set 150 kW is highly explosive. Do
not smoke or use open flame when performing maintenance.
Fire and explosion could occur, resulting in severe personal
injury or death.
Use only the pump method to hot refuel the generator set.
Do not use the open port/manual refueling method for hot
refueling. Fuel spills during hot refueling cause fire
hazards.
2 - 4 5