d. Using terminal nut wrench (3, Figure 2-4) loosen
terminal nuts (1) on terminals (2) selected in Step b.
e. Insert ends of load cables through load cable en-
trance box. Insert ends of cables into slots of load
terminal studs (2).
f. Tighten load terminal nuts (1).
g. Secure wrench (3) in bracket inside load terminal
board door, and close door.
When using single phase connections, always
attempt to balance loads between terminals (do
not connect all loads between one terminal and
LO). Failure to observe this caution can result
in damage to generator set.
Table 2-4. Load Terminal, AC Reconnection Board and AM-VM Transfer Switch Selection
RECONNEC-
TION
BOARD
POSITION
120/208
240/416
TERMINALS
AM-VM
TRANSFER
SWITCH
POSITION
VOLTAGE
READING
CURRENT
READING
(TERMINAL)
L1, L2, L3, L0 3
PHASE.
(SINGLE PHASE
LOADS CAN BE
SERVED USING ANY
TERMINAL TO L0)
L1-L0
L2-L0
L3-L0
L1-L2
L2-L3
L3-L1
120 VOLTS
120 VOLTS
120 VOLTS
208 VOLTS
208 VOLTS
208 VOLTS
L1
L2
L3
NONE
NONE
NONE
L1, L2, L3, L0 3
PHASE.
(SINGLE PHASE
LOADS CAN BE
SERVED USING ANY
TERMINAL TO L0)
L 1 -L0
L2-L0
L3-L0
L1-L2
L2-L3
L3-L1
240 VOLTS
240 VOLTS
240 VOLTS
416 VOLTS
416 VOLTS
416 VOLTS
L1
L2
L3
NONE
NONE
NONE
2-18 Change 1