Item
No.
Interval
B
D
A
20
21
22
23
ARMY TM 9-6115-644-10
AIR FORCE TO 35C2-3-446-11
MARINE CORPS TM 092494/09246A-10/1
Table 2-3. Operator Preventive Maintenance Checks and Services - Continued
B - BEFORE
D-DURING
A-AFTER
Item to
be inspected
CONTROL BOX
ASSEMBLY
Indicators and
Controls
Control Box Harness
Parallel Cable
Ground Rod Cable
and Connection
Procedures
Check for and have
repaired or adjusted
as necessary
Check all indicators and controls for
damaged or missing parts.
Ensure all indicators are operating
properly.
Check for loose or damaged wiring.
If required for generator set operation,
inspect parallel cable for damage.
ENSURE generator set is properly
grounded prior to starting. Otherwise
serious injury or death could result by
electrocution.
Inspect ground rod and cable for loose
connections, breaks, damage and
corrosion.
Equipment is
not ready/
available if:
Indicators or
controls damaged or
missing.
Frequency or AC
Voltmeter
inoperative.
Loose or damaged
wires.
Cable is missing or
damaged.
Change 1
2-15