ARMY TM 9-6115-643-24
AIR FORCE TO 3562-3-445-22
e.
Strip wires on in-line fuse holder (2, FIGURE 2-13.1) and install butt splices (3) at each end. Connect
ends of black wire to in-line fuse holder butt splices (3).
f.
Install fuse (1) in fuse holder (2)
g.
Secure excess wire to wiring harness using tie wrap
h.
Install malfunction indicator panel (27, FIGURE 2-14), screws (24). washers (25), and nuts (26)
i.
Reconnect negative battery cable and close battery access door
NOTE
When replacing GROUND FAULT CIRCUIT INTERRUPTER, use new GROUND
FAULT CIRCUIT INTERRUPTER with integral circuit breaker
Refer to TM 9-6115-
643-24P for new part number.
FIGURE 2-13.1. In-Line Fuse Installation
2.46.4. Installation.
a.
Install GROUND FAULT CIRCUIT INTERRUPTER (23, FIGURE 2-14) in malfunction indicator panel
with screws (21) and nuts (22).
b.
Connect electrical leads to TB4 and KS, and convenience receptacle (20). Remove tags.
c. Connect negative battery cable. Close battery access door.
2.47. MALFUNCTION INDICATOR PANEL.
2.47.1. Inspection.
a. Shut down generator set.
b.
Inspect malfuction indicator panel for broken indicator lights, cracked housing, corrosion, and other
damage.
2.47.2.
Testing.
a.
Depress TEST/RESET button and check that all indicators are lit.
b.
Replace malfunction indicator panel if one or more indicators do not light.
Change 4 2-78.1/(2-78.2 blank)