ARMY TM 9-6115-643-24
AIR FORCE TO 35C2-3-445-22
c.
Install CONVENIENCE RECEPTACLE cover (17) with screws (15) and nuts (16).
d.
Install control box top panel, paragraph 2.15.4.
e
Connect negative battery cable Close access
door
2.46. GROUND FAULT CIRCUIT INTERRUPTER.
2.46.1.
Inspection.
a. Shut down generator set
b
Inspect GROUND FAULT CIRCUIT INTERRUPTER for cracks, corrosion, frayed wires, and other
damage
2.46.2.
Testing.
a
Start and operate generator set at rated voltage and frequency
b
Set multimeter for AC volts, press TEST button and check for zero voltage at CONVENIENCE
RECEPTACLE.
c
Press RESET button on GROUND FAULT CIRCUIT INTERRUPTER and use multimeter to check for
120 VAC at CONVENIENCE RECEPTACLE.
d
If indications are other than above, replace GROUND FAULT CIRCUIT INTERRUPTER.
2.46.3.
Removal.
a. Shut down generator set
b
Open battery access door and disconnect negative battery cable.
c
Tag and disconnect GROUND FAULT CIRCUIT INTERRUPTER (23, FIGURE 2-14) electrical leads
from TB4 and KS, and convenience receptacle (20).
d
Remove screws (21) and nuts (22)
e.
Remove GROUND FAULT CIRCUIT INTERRUPTER (23) from malfunction indicator panel.
2.46.3.1. In-Line Fuse Installation.
NOTE
The following procedure applies to generator sets under contract number DAAK01-
88-D-D082.
a. Shut down generator set.
b
Open left side engine access door and disconnect negative battery cable
c.
Remove malfunction indicator panel screws (24, FIGURE 2-14), washers (29, and nuts (26). Lay
malfunction indicator panel to the side
d
Cut black wire on load side of GROUND FAULT CIRCUIT INTERRUPTER (23)
2-78 Change 4