ARMY TM 9-6115-639-13
AIR FORCE TO 35C2-3-386-51
MARINE CORPS TM 10155A-13/1
Table 3-3. Operator Level Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
13. NO POWER AT CONVENIENCE RECEPTACLE
a. Check that GROUND FAULT CIRCUIT INTERRUPTER (GFCI) is not tripped.
Reset GFCI by depressing button.
b. Check that 10 amp circuit breaker (located on back of GFCI) is not tripped.
Reset circuit breaker if tripped
c. Refer trouble to unit level maintenance.
Section III. OPERATOR MAINTENANCE PROCEDURES
3-4. GENERAL.
This section contains information on the generator set maintenance tasks that are the responsibility of the
operator. If a procedure is not located in this chapter, you are not authorized to perform it.
Never service, inspect, or perform maintenance on the generator set
while the engine is running. Always shut down the unit before servicing.
Allow engine to cool before handling components. Failure to observe
this warning can result in severe burn or injury.
3-5. GENERATOR SET ENCLOSURE AND COVER.
a. Inspect the enclosure assembly for missing or loose components, cracks, dents, or other damage.
b. Check cover latches to ensure that they are properly secured. Check for proper operation, free of
binding. Ensure that latches lock cover securely.
c. Open enclosure cover. Check that pistons hold cover in place. Inspect cover insulating material for
damage and security of attachment. Close enclosure cover and lock using latches.
d. If damage is found, notify unit level maintenance personnel for repair.