Table 3-3. Operator Level Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
7.
LOW OIL PRESSURE INDICATOR ILLUMINATES DURING OPERATION
a. Check engine oil level.
Service as required (para. 3-1). Press FAULT RESET pushbutton to reset fault
indicator module.
b. Refer trouble to unit level maintenance.
8.
NO FUEL INDICATOR ILLUMINATES
a. Check fuel tank level (refer to para. 3-7).
Service fuel tank as required. Press FAULT RESET pushbutton to reset fault indicator
module.
b. If operating on AUX FUEL, check that AUX FUEL switch is in ON position.
Place switch in ON position. Press FAULT RESET pushbutton to reset fault indicator module.
c. Refer trouble to unit level maintenance.
9.
GENERATOR SET CAUSES RADIO INTERFERENCE
a. Check that load terminals and cables are connected tightly.
Tighten connections using load wrench supplied.
b. Check that ground wire is connected tightly.
Tighten connection using load wrench supplied.
c. Check that ground rod is properly installed and operational.
Replace ground rod.
d. Refer trouble to unit maintenance level.
3-7
Change 1