ARMY TM 9-6115-639-13
AIR FORCE TO 35C2-3-386-51
MARINE CORPS TM 10155A-13/1
Section I. LUBRICATION INSTRUCTIONS
4-1. GENERAL.
a. These lubrication instructions are for unit level maintenance personnel. Lube intervals (on-condition
or hard time) are based on normal operation. Lube more during constant use, and less during inactive periods.
Use correct grade of lubricant for seasonal temperature expected.
CAUTION
Always wipe clean oil filler components before starting your lube
service. Use correct type or grade of oil. Overfilling will cause spillage
and harm engine components.
b. The engine oil filter shall be changed as applicable when:
(1)
It is known to be contaminated or clogged.
(2)
The prescribed hard time interval has arrived.
c. This generator set is not enrolled in the Army Oil Analysis Program (AOAP). Hard time service
intervals apply.
d. For equipment under manufacturers warranty, hard time oil service intervals shall be followed.
Intervals shall be shortened if lubricants are known to be contaminated or if operation is under adverse
conditions (such as longer than usual operating hours, extended idling periods, or extreme dust).
Table 4-1. Lubricant Table for Generator Set MEP 831A / 832A
Lubrication Mil. Symbol
Specification
Temperature Range
System
Capacity
Interval
Man-
hours
MIL-L-46167, OEA
MIL-L-2104, OE/HDO-15/40
MIL-L-2104, OE/HDO-10
MIL-L-2104, OE/HDO-30
MIL-L-2104, OE/HDO-40
-25F to +40F (-31C to +5C)
+5F to +120F (-15C to +49C)
-15F to +40F (-26C to +5C)
+15F to +90F (-9C to +32C)
+30F to +120F (-1C to +49C)
1.2 qts. (1.1 ltrs.)
1.2 qts. (1.1 ltrs.)
1.2 qts. (1.1 ltrs.)
1.2 qts. (1.1 ltrs.)
1.2 qts. (1.1 ltrs.)
100 hours
100 hours
100 hours
100 hours
100 hours
0.25
0.25
0.25
0.25
0.25
4-3