ARMY TM 9-6115-639-13
AIR FORCE TO 35C2-3-386-51
MARINE CORPS TM 10155A-13/1
4-52. POWER INVERTER / CONVERTER MAINTENANCE - cont.
B. INSPECTION.
1.
Inspect power inverter / converter for obvious
damage. Inspect for corrosion and evidence of
electrical short. Check air ducts for clogs or
obstructions. Clear obstructions.
2.
Inspect electrical wiring for cuts, crimps, bare
wire, or other damage. Ensure terminal lugs are
securely attached.
3.
Repair of the power inverter / converter is limited
to removal and replacement of the assembly. All
adjustments are factory set and may not be
altered.
4.
Remove and replace any component that is
damaged to the extent that it will effect the safe
operation of the generator set.
C. INSTALLATION.
1.
Carefully install power inverter / converter (5,
Figure 4-47) into generator set enclosure.
2.
Install bracket (17) onto inverter / converter (5)
using two screws (21), lockwashers (22), and
washers (23). Secure bracket to skid base using
four screws (18), lockwashers (19), and washers
(20).
3.
Mate inverter / converter (5) to rear wall of
enclosure (13). Secure using six screws (14),
lockwashers (15), and washers (16).
4.
Attach inverter / converter (5) to bracket (9) using
two screws (10), lockwashers (11), and washers
(12).
5.
Secure control box to bracket (9) using two
screws (6), lockwashers (7), and washers (8).
Figure 4-47. Power Inverter / Converter
(Sheet 1 of 2)
4-129