TM 55-6115-491-40
SECTION II
TEST EQUIPMENT, SPECIAL TOOLS, AND MATERIALS
2-1. GENERAL.
2-3. TEST EQUIPMENT.
2-2. This section lists all test equipment, special tools
2-4.
Test equipment required for general support
and consumable materials required to perform general
maintenance of the generator is listed in table 2-1.
support maintenance for the generator.
Table 2-1. Test Equipment Required (Sheet 1 of 3)
PART, MODEL,
OR MILDES
NOMENCLATURE
TECHNICAL
(OR EQUIVALENT)
DESCRIPTION
Drive motor
A prime mover having a speed range up to approximately 10,000
revolutions per minute and a minimum rating of 50 horsepower.
Motor will be capable of driving the generator continuously
under full load conditions.
Speed indicator
Tachometer capable of indicating rotating speeds up to 10,000
revolutions per minute.
Table 2-1. Test Equipment Required (Sheet 2 of 3)
PART, MODEL,
OR MILDES
NOMENCLATURE
TECHNICAL
(OR EQUIVALENT)
DESCRIPTION
Air blower
Capable of delivering air at a total pressure (static plus velocity
head) of 1.6 inches of water (measured 12 inches from the
entrance of blast cap) including means to supply the cooling air
at a temperature of 77'F:t27oF (250C150C). Air pressure
can be controlled by placing an adjustable clamp over a fabric
hose connection.
Manometer
Manometer calibrated in inches of water should be used for in-
dicating air pressure.
Thermocouple
Thermocouples and associated indicators to measure frame
temperatures.
Instruments
Direct-current ammeter with a 0-5 ampere range for measure AC
generator field current and PM generator output.
Alternating-current ammeters with a 0-200 ampere range for
Alternating-current voltmeter having a range of 0-300 volts and a
selector switch for measuring the line-to-line output voltage.
Table 2-1. Test Equipment Required (Sheet 3 of 3)
PART, MODEL,
OR MILDES
NOMENCLATURE
TECHNICAL
(OR EQUIVALENT)
DESCRIPTION
A frequency meter having a range of 0 to 500 cycles per second.
A phase sequence indicator to measure the direction of phase
rotation.
Alternating-current wattmeters to measure the output power.
Direct-current voltmeter having a range of 0-50 volts for
measuring PM generator output.
LSI 51250-010
Voltage regulator
Electronic voltage control unit.
LSI 50185-010
Control panel
To control generator output.
Line contactor
Capable of closing and interrupting up to 40 KVA of 120/ 208
volt alternating-current power.
2-1