TM 5-6115-631-14&P
Table 4-1. Unit Preventive Maintenance Checks and Services (PMCS). CONT.
H Hours of operation
W Weekly
M Monthly
(As indicated)
S - Semiannually
A Annually
(40 hours)
(100 hours)
(500 hours)
(1000 hours)
Interval
Item to be
Inspected
Generator Set
Fuel Strainer and
Filters
Fuel Tank
Procedures
WARNING
Before performing any maintenance
that requires climbing on or under
trailer, set trailer handbrakes, chock
wheels, and lower rear leg prop.
Injury to personnel could result
from trailer suddenly rolling or
tipping.
NOTE
Generator set checks and services in
this table are described as performed
on a single generator set. These
procedures must be performed
on each of the two generator sets
that make up the AN/MJQ-16.
Inspect generator set for fuel and oil
leaks, loose or missing components and
hardware, and unusual wear or
deterioration. Clean generator set.
NOTE
Fuel system must be above freezing
temperature when draining water
and sediment from strainer, filters,
and tank.
Open drains on fuel strainer, and
secondary filters. Drain water and
sediment (table 3-2, TM 5-61 15-584-12)
Allow to drain until fuel runs clean.
Open drain on fuel tank and drain water
and sediment (table 3-2, TM 5-6115-
584-12). Allow to drain until fuels runs
clean.
Change 1
4-9