TM 9-6150-228-13&P
NOTES:
1.
ALL DIMENSIONS ARE IN INCHES, WITH METRIC EQUIVALENT IN PARENTHESES.
2.
CUT AND REMOVE WIRE INSULATION FROM ENDS AS INDICATED.
3.
CABLE WILL BE TYPE HDE OR HDF PER MIL-C-3432.
4.
WIRE SIZES WILL BE AS FOLLOWS:
CONFIGURATION
SIZE
PHASE A
250 MCM
PHASE B
250 MCM
PHASE C
250 MCM
NEUTRAL
250 MCM
GROUND
NO. 1/0 AWG
5.
GROUND CABLE SHALL BE A MINIMUM 4 FEET LONGER THAN CABLE ASSEMBLY LENGTH.
6.
THE FIVE SINGLE-CONDUCTOR STRANDED CABLES THAT MAKE UP THE POWER INPUT CABLE KIT ARE
BANDED FOR CORRECT PHASING AS FOLLOWS:
MARKING BAND INFORMATION
BLACK
PHASE A
RED
PHASE B
BLUE OR ORANGE
PHASE C
WHITE
NEUTRAL
GREEN (If insulated)
GROUND
Figure G-3. Power Input Cable Assembly.
G-10