TM 9-6150-228-13&P
Do not reply on the color of the wire insulation for phase color-coding. The
insulation on the wires inside the cable jacket may vary, depending on the
supplier. Wires will be marked with colored tape to designate the phases.
Perform a continuity test to verify correct phase designation in accordance with
the colored tape.
NOTES:
1.
ALL DIMENSIONS ARE IN INCHES, WITH THE METRIC EQUIVALENT IN PARENTHESES.
2.
CUT AND REMOVE CABLE AND WIRE INSULATION FROM CABLE ENDS AS INDICATED.
3.
TWIST FOUR GROUND WIRES TOGETHER.
4.
INSTALL P1 AND P2 CONNECTORS ON PROPER CABLE ENDS SO COLORS AND PINS/SOCKETS MATCH
AS FOLLOWS:
COLOR
FROM
TO
BLACK
P1-A
P2-A
RED
P1-B
P2-B
BLUE OR ORANGE
P1-C
P2-C
WHITE
P1-N
P2-C
GREEN (OR BARE)
P1-G1
P2-G1
GREEN (OR BARE)
P1-G2
P2-G2
GREEN (OR BARE)
P1-G3
P2-G3
GREEN (OR BARE)
P1-G4
P2-G4
5.
VERIFY ELECTRICAL CONTINUITY FOR EACH "FROM-TO" PATH WITH AN OHMETER.
6.
CRIMP PINS/SOCKETS TO CABLE WIRES. SEE TABLE G-1 AND G-2.
7.
ASSEMBLE P1 AND P2 CONNECTORS SO KEYS(KEY-WAYS AND PIN/SOCKETS ALIGN AS INDICATED.
8.
MARK SLEEVES IN ACCORDANCE WITH MIL-M-60903 AS FOLLOWS:
120/208 VAC
3-PHASE
60-AMP
Figure G-2. 100-Amp, 50 Ft. (15.2m) Power Cable (Sheet 3 of 3).
G-9