TM 9-6150-226-13
(1) The total load must not exceed 7.2 kW.
(2) The generator selected must be capable of supporting the total
load.
(3) Individual branch circuit loads must not exceed 2.4 kW. Three
of the six outputs, carrying maximum load, can be used at the same time.
b.
Three-Phase Input Systems.
(1) M200 and M200 A/P.
The 200-amp,
3-phase electrical feeder
system (Fig.
1-3) can be used as a stand-alone system with the following
provi
total
sions:
(a) The total load must not exceed 72 kW.
(b) The generator selected must be capable of supporting the
load.
(c) Individual branch circuit output loads must not exceed:
1 36 kW for the 100-amp. 3-phase branch circuits. Two of
the three outputs, carrying maximum load, can- be used at the same time.
2 21.6 kW for the 60-amp, 3-phase branch circuits. Three
of the four outputs, carrying maximum load, can be used at the same time.
3 2.4 kW for the 20-amp, single-phase branch circuit.
(2) M1OO and M1OO A/P.
The 100-amp,
3-phase electrical feeder
system (Fig.
1-4) can be used as a stand-alone system with the following
provisions:
(a) The total load must not exceed 36 kW.
(b) The generator selected must be capable of supporting the
total load.
(c) Individual branch circuit output loads must not exceed:
1
36 kW for the 100-amp,
3-phase feed-through circuit.
This uses the total system capacity and no other outputs can be used.
2 21.6 kW for the 60-amp, 3-phase branch circuits. Only
one of the two outputs, carrying maximum load, can be used at the same time.
3 14.4 kW for the 40-amp, 3-phase branch circuits. Both
outputs, carrying maximum load, can be used at the same time.
4
2.4 kW for the 20-amp, single-phase circuits.
Both
outputs, carrying maximum load, can be used at the same time.
1-20