TM 9-6150-226-13
(b) Cables are equipped with military standard connectors which
mate according to amperage rating.
Cables designed for different amperages
will not connect.
(c) Cables are equipped with covers to protect the connectors
from moisture and dirt.
WARNING
High voltage is present in this system. DISE and
PDISE supports equipment using 120/208 V ac. Do
not rely on the color of the wire insulation for
phase color-coding.
The insulation on the wires
inside the cable jacket may vary, depending on
supplier.
Wires will be color coded to designate
the phases.
If the wire color coding cannot be
determined,
notify next higher level of main-
tenance to perform continuity test.
Perform a
continuity
test to
verify
correct
phase
designation in accordance with identified color.
(d) Cable wires are color-coded as follows:
1 Phase A (L1)-Black
2 Phase B (L2)-Red
3 Phase C (L3)-Blue
4 Neutral N (LO)-White
5 Ground G-Green or bare wire
(3) Systems.
Systems are designed to provide correct phase,
neutral, and ground matching.
1-13.
EQUIPMENT DATA.
a.
Table 1-1 lists equipment data for each of the DISE and PDISE
feeder/distribution centers.
b.
Tables 1-2 and 1-3 list equi
There are other auxiliary
PDISE systems (see para 2-9).
pment data for the DISE and PDISE cables.
items that supplement the five DISE and
1-16