TM 9-6115-730-24
0011
TROUBLESHOOTING FAILURES WITHOUT FAULT CODES - Continued
MALFUNCTION
Fuel Supply Problem.
CORRECTIVE ACTION
STEP 1.
Perform Injector Solenoid Test and Cylinder Cutout Test (WP 0013,
STEP 2.
Check for a fuel supply problem and verify fuel pressure (WP 0013,
SYMPTOM 10).
MALFUNCTION
Generator Malfunction.
CORRECTIVE ACTION
STEP 1.
On EMCP set ENGINE CONTROL switch to OFF/RESET. Set Battery
Disconnect Switch to OFF. Set DEAD CRANK SWITCH to OFF.
STEP 2.
Inspect generator for problems or restrictions that would place excess load on
engine. Visually check generator rotor shaft for excessive play, vibration, or
STEP 3.
Verify the problem has been resolved.
SYMPTOM
29.
Engine Stalls at Low RPM.
MALFUNCTION
Electrical Connections Faulty.
CORRECTIVE ACTION
STEP 1.
On EMCP set ENGINE CONTROL Switch to OFF/RESET. Set Battery
Disconnect Switch to OFF. Set DEAD CRANK SWITCH to OFF.
STEP 2.
Check for correct installation of engine harness ENG-P2 connector to ECM J2
and engine harness connector ENG-P300 to fuel injector harness connector
STEP 3.
Verify the problem has been resolved.
0011-38