TM 9-6115-730-24
FIELD LEVEL TROUBLESHOOTING
TACTICAL QUIET GENERATOR 200 kW, 50/60 Hz MEP-809A/PU-809A
GSC FAULT CODE TROUBLESHOOTING PROCEDURES
INITIAL SETUP:
Tools and Special Tools
References
FO-1
FO-2
Personnel Required
FO-3
One
FO-4
TM 9-6115-730-10
TROUBLESHOOTING USING GSC FAULT CODES
WARNING
Metal jewelry will conduct electricity. All jewelry can become entangled in generator set
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
High voltage is produced when this generator set is in operation. Make sure unit is completely
shut down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
DC voltages are present at generator set electrical components even with generator set shut
down. Avoid shorting any positive with ground/negative. Failure to comply can cause injury to
personnel and damage to equipment.
Ensure that the engine cannot be started while maintenance is being performed. (ENGINE
CONTROL switch set to OFF/RESET. Battery Disconnect Switch is OFF; DEAD CRANK
SWITCH is OFF.)
0009-1