TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR SET
0007 00
OPERATION UNDER UNUSUAL CONDITIONS Continued
OPERATION USING BATTLE SHORT SWITCH
CAUTION
Continued operation using the BATTLE SHORT switch can result in damage to the generator set.
NOTE
If any emergency situation requires continued operation of the generator set, the BATTLE SHORT switch
is used to override all protection devices except the overspeed, short circuit devices, and EMERGENCY
STOP function.
BATTLE SHORT switch must be OFF to start generator set.
1.
On EMCP, set BATTLE SHORT switch to OFF.
2.
On EMCP, set ENGINE CONTROL switch to MANUAL START.
3.
Once generator set starts, lift cover on BATTLE SHORT switch and set to ON.
CAUTION
If the ENGINE OVERSPEED light on the malfunction indicator panel is illuminated, set AC
CIRCUIT INTERRUPTER to OPEN (down) until indicator goes out on each set.
END OF TASK
OPERATION WHILE CONTAMINATED (NBC)
capable of being operated by personnel wearing NBC clothing without special tools or support equipment. Refer to FM 3-3, FM
3-4, and FM 3-5.
END OF TASK
0007 00-6