TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR SET
0006 00
OPERATION UNDER USUAL CONDITIONS Continued
OPERATING PROCEDURES Continued
Stopping Procedure
1.
To remove load on EMCP, set AC CIRCUIT INTERRUPTER (5) switch to OPEN (down).
NOTE
ENGINE CONTROL switch may be set to MANUAL START to continue operation by turning
counterclockwise.
2.
Set ENGINE CONTROL (2) switch to COOL DOWN/STOP. This will allow generator set to operate with no load
applied for 5 minutes. The generator set will shut down automatically.
3.
Set ENGINE CONTROL (2) switch to OFF/RESET.
4.
5.
6.
Open battery compartment and set Battery Disconnect Switch to OFF (WP 0005 00-14).
END OF TASK
EMERGENCY STOPPING
1.
Press PUSH TO STOP EMERGENCY STOP (14) pushbutton to stop generator set.
2.
Set ENGINE CONTROL switch to OFF/RESET.
END OF TASK