TM 9-6115-729-24
0085
REPROGRAMMING GSC SETPOINTS FOR VOLTAGE AND FREQUENCY CHANGE - Continued
22. Repeat steps 18 through 21 until all setpoint values are checked or changed for OP5-0.
23. Repeat steps 16 through 22 for OP5-1. The first setpoint displayed will be P101. The first setpoint to be
changed/verified is P114, per Table 3.
24. At the completion of the programming, press EXIT key until SERV is no longer displayed on upper display.
25. If the generator set is not to be used, set ENGINE CONTROL Switch (ECS) to OFF/RESET, set DEAD
CRANK SWITCH to OFF, and set Battery Disconnect Switch to OFF.
END OF TASK
0085-10