TM 9-6115-729-24
0085
REPROGRAMMING OR VERIFYING DVR PARAMETERS - Continued
key on DVR once to switch back to the parameter number.
13. Press Function
once to change to next parameter number per Table 2.
14. Press up arrow key
15. Keep repeating from step 7, entering or viewing parameter data from Table 2, until all parameter data is
entered or verified to be correct.
key on DVR once to display data for parameter :90.
16. Press Function
or down arrow key
to set the data for parameter number :90 to any
17. Press and hold up arrow key
number but 0009 to lock the DVR. DVR will not stay locked when Engine Control switch is switched from
either COOL DOWN/STOP to OFF/RESET and back to COOL DOWN/STOP or from COOL DOWN/STOP to
MANUAL START.
18. If the generator set is not to be used, set ENGINE CONTROL Switch (ECS) to OFF/RESET, set DEAD
CRANK SWITCH to OFF, and set Battery Disconnect Switch to OFF.
END OF TASK
0085-7