TM 9-6115-729-24
0085
REPROGRAMMING DVR PARAMETERS FOR VOLTAGE AND FREQUENCY CHANGE - Continued
. DVR display should read :01 (the colon with the number indicates that the
5. Press the up arrow key
number is a parameter number).
until display shows parameter number :90. Parameter number: 90 is a
6. Press and hold up arrow key
password that can be used to protect the settings.
key on DVR once to display data for parameter :90.
7. Press Function
or down arrow key
to set the data for parameter number :90 to 0200.
8. Press and hold up arrow key
9. Press Function
key on DVR once to display parameter :90.
or down arrow key
to change to parameter number :01.
10. Press and hold up arrow key
11. Press Function
key on DVR once to display data for parameter.
or down arrow key
to set the data for parameter per Table 1.
12. Press and hold up arrow key
13. Press Function
key on DVR once to switch back to the parameter number.
once to change to next parameter number per Table 1.
14. Press up arrow key
15. Keep repeating from step 9, entering parameter data from Table 1, until all 6 parameter data is entered or
verified to be correct.
key on DVR once to display data for parameter :90.
16. Press Function
or down arrow key
to set the data for parameter number :90 to any
17. Press and hold up arrow key
number but 0009 to lock the DVR. DVR will not stay locked when Engine Control switch is switched from
either COOL DOWN/STOP to OFF/RESET and back to COOL DOWN/STOP or from COOL DOWN/STOP to
MANUAL START.
key on DVR once to switch back to parameter number. Press and hold up arrow key
18. Press Function
or down arrow key
to set the parameter number back to 01.
19. Proceed to REPROGRAMMING GSC SETPOINTS FOR VOLTAGE AND FREQUENCY CHANGE and
reprogram the OP5 parameters for P028 thru P031 (steps 1 thru 25).
20. If the generator set is not to be used, set ENGINE CONTROL Switch (ECS) to OFF/RESET, set DEAD
CRANK SWITCH to OFF, and set Battery Disconnect Switch to OFF.
END OF TASK
0085-2