TM 9-6115-729-24
UNIT (FIELD) LEVEL MAINTENANCE
TACTICAL QUIET GENERATOR 100 kW, 50/60 Hz MEP-807A/PU-807A
LEFT FRONT DOOR ASSEMBLY (LATCH) MAINTENANCE
INITIAL SETUP:
Tools and Special Tools
References
Tool Kit, General Mechanic's (WP 0119, Item 1)
TM 9-6115-729-24P
Personnel Required
Equipment Condition
One
Grounding rods removed (TM 9-6115-729-10)
Materials/Parts
WARNINGS
Metal jewelry will conduct electricity. All jewelry can become entangled in generator set
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
DO NOT wear loose clothing when performing checks, services and maintenance. Failure to
comply can cause injury or death to personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
REMOVAL
1. Turn two latches (Figure 1, Item 1) and open left front door assembly (latch) (Figure 1, Item 2).
2. Remove twelve screws (Figure 1, Item 3), washers (Figure 1, Item 4), lockwashers (Figure 1, Item 5), and left
front door assembly (latch) and hinge (Figure 1, Item 2).
END OF TASK
DISASSEMBLY
1. Remove eight nuts (Figure 1, Item 6), screws (Figure 1, Item 7), and two latches (Figure 1, Item 1).
0021-1