TM 9-6115-729-24
0016
Table 1. Preventive Maintenance Checks and Services - Continued.
ITEM TO BE
CHECKED
EQUIPMENT
ITEM
MAN-
OR
NOT READY/
NO.
INTERVAL
HOUR
SERVICED
PROCEDURE
AVAILABLE IF:
11
Quarterly or
Main Load
Check main load contactor for
Any defect that would
300 hours
Contactor K1
corrosion, loose or missing parts,
prevent operation.
loose cable connections, evidence of
12
Quarterly or
Current
300 hours
Transformers
corrosion, loose or missing parts,
prevent operation.
loose connections, evidence of arcing
or overheating, leaking, or loose
13
Quarterly or
Power
300 hours
Transformers
corrosion, loose or missing parts,
prevent operation.
loose connections, evidence of arcing
or overheating, leaking, or loose
14
Quarterly or
Slave
Check slave receptacle for corrosion,
Any defect that would
300 hours
Receptacle
loose or missing parts, loose
prevent operation.
connections, evidence of arcing or
overheating, or loose mounting
15
Quarterly or
Electrical
Check electrical components for
Any defect that would
300 hours
Installation
corrosion, loose or missing parts,
prevent operation.
loose connections, evidence of arcing
or overheating, or loose mounting
ENGINE
16
Quarterly or
Engine Oil/Oil
Change engine oil and oil filter
Engine oil change/
300 hours
Filter
filter change not
accomplished.
17
Quarterly or
Oil Pan
Check magnetic plug for metal
Metal particles found
300 hours
on plug.
18
Quarterly or
Fuel System
Check fuel system for secure
Any leaks or defect
300 hours
mounting, leaks, damaged tubes or
that would prevent
operation. Any leak
from fuel system.
0016-3