TM 9-6115-729-10
MALFUNCTION/SYMPTOM INDEX Continued
The Malfunction/Symptom Index provides a quick reference by work package number and page number for error
messages and troubleshooting procedure malfunctions.
Work Package and Page No.
Malfunction/Symptom
Dedicated Fault Indicators
1.
EMCP AC CIRCUIT INTERRUPTER lamp does not light when TQG is
0010 00-3
connected to load.
2.
EMCP panel lamp is not lit.
0010 00-3
3.
GSC LOW OIL PRESSURE red indicator flashes.
0010 00-3
4.
GSC HIGH WATER TEMP red indicator flashes.
0010 00-4
5.
GSC LOW COOLANT LEVEL red indicator flashes.
0010 00-5
6.
Alarm module OVERCURRENT amber indicator flashes. TQG disconnects
0010 00-5
from load.
7.
Alarm module GENERATOR OVERLOAD amber indicator flashes. TQG
0010 00-6
disconnects from load.
8.
Alarm module LOW FUEL LEVEL red indicator glows steady. TQG engine
0010 00-7
shuts down.
9.
Convenience receptacle on PARALLELING RECEPTACLES panel has no
0010 00-8
power.
10.
Winterization kit (issued to selected units only) is not operating.
0010 00-8
DIAGNOSTIC light is red.
GSC Alarm Fault Codes
11.
AL1 - High Water Temperature
Troubleshoot as Malfunction 4,
0010 00-4.
12.
AL2 - Low Water Temperature
AL2 can be a transient code that
will go away after the TQG is
running. If not, notify
maintenance.
13.
AL3 - Low Engine Oil Pressure
Troubleshoot as Malfunction 3,
0010 00-3.
14.
AL4 - Fault Detected by Engine ECM
Notify maintenance.
15.
AL5 - Low Engine Coolant Level
Troubleshoot as Malfunction 5,
0010 00-4
16.
AL6 - High Engine Oil Temperature
Troubleshoot as Malfunction 3,
0010 00-3. Notify
maintenance.
17.
AL7- Generator Over Voltage
Notify maintenance.
18.
AL8 - Generator Under Voltage
Notify maintenance.
0009 00-1