ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
4-182
__________
WARNING
DC voltages are present at generator set electrical components even with
generator shut down. Avoid shorting any positive terminal with
ground/negative. Failure to comply can cause injury to personnel and damage
to equipment.
(1)
Open left side engine compartment access doors (Figure 1-2).
(2)
Install spray nozzle (11, Figure 4-27) on engine intake manifold.
(3)
Install adapter (19) into solenoid (3).
(4)
Install solenoid (3) to bracket (18) with bolts (17).
(5)
Install relay (16), bolts (15), washers (14), lockwashers (13), and bolts (12) on generator set
housing.
(6)
Remove cap (4) from ether solenoid valve (3).
(7)
Insert ether cylinder (2) through cylinder bracket assembly (8), and screw cylinder into ether
solenoid valve (3).
(8)
Close clamp of cylinder bracket assembly (8), and tighten wingnut (1).
(9)
Connect tube assembly (10) to adapter (19) and spray nozzle (11).
(10) Connect electrical leads to ether solenoid valve (3). Remove tags.
(11) Connect negative battery cable to battery, and close BATTERY ACCESS door.
(12) Close engine compartment access doors.
4.11.9 Ether Solenoid Relay.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open right side engine compartment access doors (Figure 1-2).
(3)
Inspect ether solenoid relay (16, Figure 4-27) for cracks, loose mounting and other damage.
(4)
Replace damaged parts.
(5)
Close engine compartment access doors.
b. Removal.