4-184
(4) Close drain cock (2, Fig. 3-5) and air vent (1, Fig. 3-5).
(5) Close engine compartment access doors.
c. Removal.
(1) Refer to engine manual 9-6115-672-24, Paragraph 3.12.2.
d. Installation.
(1) Refer to engine manual 9-6115-672-24, Paragraph 3.12.2.
4.12.
MAINTENANCE OF OUTPUT BOX ASSEMBLY.
__________
WARNING
When disconnecting or removing batteries, disconnect the negative lead that
connects directly to the grounding stud first. Disconnect the negative end of
the interconnection cable next. When installing batteries, reverse the
connection sequence. Failure to comply can cause serious personal injury.
4.12.1 Voltage Reconnection Terminal Board TB1.
a. Inspection.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Open battery access door (Figure 1-2) and disconnect negative cable.
(3)
Open output box access door (Figure 1-2).
(4)
Inspect protective cover (3, figure 4-28) and moveable terminal board (6) for cracks, breaks,
corrosion, and other damage.
(5)
Replace defective parts.
(6)
Connect negative battery cable to battery and close battery access door.
(7)
Close output box access door.
b. Removal.
(1)
Shut down generator