TABLE 4-3. UNIT PREVENTIVE MAINTENANCE CHECKS AND
SERVICES (PMCS) (continued)
M - Monthly Q - Quarterly S - Semi-annually A - Annually B - Biannually H - Hours
Interval
Item
No.
M
Q
S
A
B
H
Item to be
inspected
Procedures
Check for and have repaired or
adjusted as necessary
Equipment is
not ready/
available if:
8
300
Crankcase
Breather Filter
Assembly
Inspect and service. Refer to
paragraph 4.9.6.
9
Hardware and
sound
insulation
Inspect for loose, damaged, or
missing hardware and sound
insulation. tighten loose
hardware. Repair or replace
damaged or missing hardware or
insulation. Refer to paragraph
4.7.
Loose,
missing, or
damaged
hardware or
insulation.
10
Radiator and
interior of
generator set
Clean radiator exterior surfaces.
Refer to paragraph 4.10.7.
11
Magnetic
pickup
Remove, inspect, and clean
magnetic pickup. Refer to
paragraph 4.13.3.
Magnetic
pickup is
damaged.
12
Wiring
harnesses
Check wiring harnesses for
breaks and loose connections.
Repair and tighten wiring
harnesses as necessary.
Wiring
harnesses are
damaged or
connections
are loose.
13
Muffler
Check muffler for leaks,
restriction, and accumulation of
carbon. Replace or clean as
required. Refer to paragraph
4.9.1.
Muffler leaks,
is restricted, or
has excessive
carbon
accumulation.
NOTE
If the auxiliary fuel system is used as the primary fuel source, the auxiliary fuel
filter must be replaced semi-annually.
14
500
Auxiliary fuel
filter
Check for proper operation using
the auxiliary system as primary
source. Refer to paragraph
4.11.2.