ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
4-5
__________
WARNING
Fuels used in the generator set are flammable. When filling the fuel tank,
maintain metal-to-metal contact between filler nozzle and fuel tank opening to
eliminate static electrical discharge. Failure to comply can result in flames and
possible explosion and can cause injury or death to personnel and damage to
the generator set.
(3)
Fill fuel tank with fuel type in accordance with Table 4-2. Fuel tank capacity is 43 gallons (162.75
liters).
TABLE 4-2. FUEL
AMBIENT TEMPERATURE
DIESEL FUEL
+20°F TO 120°F
(-6°C TO +49°C)
VV-F-800 GRADE DF-2, JP5, OR JP8
0°F TO +20°F
(-17°C TO -6°C)
VV-F-800 GRADE DF-1, JP5, OR JP8
-25°F TO 0°F
(-32°C TO -17°C)
VV-F-800
GRADE DF-1
-25°F TO 0°F
(-32°C TO -17°C)
VV-F-800
GRADE DF-A
(4)
Install fuel tank filler cap.
d. Lubrication.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Place suitable container under OIL DRAIN (2, Figure 4-1), and remove plug.
(3)
Open BATTERY ACCESS door (Figure 1-2), and open oil drain valve. Drain oil.
(4)
Close oil drain valve, and close BATTERY ACCESS door. Install plug in OIL DRAIN (2).
(5)
Remove oil fill cap (1, Figure.4-2).
CAUTION
Oil dipstick is marked ENGINE OFF on one side and ENGINE ON on the
other so crankcase oil can be checked with the engine in either condition.
Ensure the appropriate side of the dipstick is used when checking oil level.
Failure to comply can cause damage to equipment.
(6)
Fill engine with proper engine lubricating oil to FULL mark on dipstick (2). Refer to Appendix F.
Lubrication system capacity is 18 quarts (17.03 liters).
(7)
Install oil fill cap (1).