TM 9-6115-669-13&P
Table 2-2 Control Cabinet Assembly, Description of Circuit Breakers.
Item
Number
Description
Protects
1
24 V DC/50 A circuit breaker, 1 pole
Circuit breakers, K4 and K28; time relay
(F1)
K10; control cabinet 24 V circuits
2
24 V DC/6 A circuit breaker, 1 pole
J2/24 V receptacle, cabinet light H7
(F2)
3
24 V DC/16 A circuit breaker, 1 pole
Speed governor assembly N1, digital iso-
(F3)
chronous load sharing module N4
4
24 V DC/6 A circuit breaker, 1 pole
Auxiliary contactor K2 (charging control
(F4)
system, oil pressure, cylinder head and oil
temperature)
5
24 V DC/6 A circuit breaker, 1 pole
OIL PRESSURE, OIL TEMPERATURE,
(F5)
FUEL LEVEL meters
6
24 V DC/6 A circuit breaker, 1 pole
FREQUENCY meter, HOURMETER meter,
(F6)
brightness control N5
7
24 V DC/16 A circuit breaker, 1 pole
Auxiliary contactors K5, K7, KS, K9, K11,
(F7)
K12, K19, K21, K23 and K27; time relays
K3 and K13; thermistor relay F12, safety
circuits
8
24 V DC/16 A circuit breaker, 1 pole
Auxiliary contactor K24 (Tank max.); FUEL
(F8)
TANK PUMP ON illuminated pushbutton
switch, FUEL TANK PUMP OFF pushbut-
ton switch
9
24 V DC/20 A circuit breaker, 1 pole
Auxiliary contactors K6, K14, K16, K18 and
(F9)
K20; time relays K25 and K26; main contac-
tor K1; voltage regulator N2; safety device
N3
10
120 V AC/6 A circuit breaker, 3 pole
(F10)
FREQUENCY, KILOWATTS and VOLTAGE
meters; voltage regulator N2; safety device
N3
11
120 V AC/16 A circuit breaker, 1 pole
J1/120 V 400 Hz double receptacle
(F11)
12
24 V DC/20 A receptacle, 1 pole
(F101)
Auxiliary contactors K101 to K105, K111,
time relays K106, K107 and K110, glow-
plug, air flap, fan motor, circuit breaker
F102
13
24 V DC/20 A circuit breaker, 2 pole
(F102)
Oil pump, HEATING FAILURE lamp H103
14
24 V DC/0,5 A circuit breaker, 2 pole
(F103)
Time relay K108, auxiliary contactor K109,
solenoid valve, HEATING FAILURE lamp
H103
2 - 9