5.15 INTERNAL POWER SUPPLY V5/T13 MAINTENANCE.
This task covers:
a
Removal
b.
Inspection c.
Test
d.
Installation
General Mechanics Tool Kit
(item 2, appendix B)
Automotive Fuel and Electrical System Repair,
Tool Kit (item 3, appendix B)
Reference
Shut down Generator Set
150 kW, paragraph 2.8.1.
AC Power Supply, 208 VAC/3-/400 Hz
None
WARNING
The Generator Sets 150 kW produce lethal voltages.
Turn off power to the EPP III or Generator Set 150 kW before
assembly work.
performing and installation, removal, disassembly, or
Wear protective gloves when performing any work on main
assemblies of the EPP III.
CAUTION
Label all cables before removing electrical or electronic assemblies or
components.
a.
Remove stanchion by PDU (1, figure 5-16).
b.
Open access door (2) and secure with prop (3).
c. Install stanchion.
RECTIFIER V5
a.
Refer to paragraph 5.17 and remove rubber flap and connection panel.
b.
Record labeling and position of cables 116, 117, and 118 from contactor K3 and remove cables.
Refer to paragraph 5.10.
c.
Record labeling and position of cables of rectifier V5 (7), loosen screw and remove cables.
d. Remove two screws (4), serrated lock washers (5), washers (6) and rectifier V5 (7). Tag and
remove cables from rectifier V5 (7).