TM 9-6115-669-13&P5.15 INTERNAL POWER SUPPLY V5/T13 MAINTENANCE.This task covers:aRemoval b.Inspection c.Testd.InstallationGeneral Mechanic’s Tool Kit(item 2, appendix B)Automotive Fuel and Electrical System Repair,Tool Kit (item 3, appendix B)ReferenceShut down Generator Set150 kW, paragraph 2.8.1.AC Power Supply, 208 VAC/3-/400 HzNoneWARNINGThe Generator Sets 150 kW produce lethal voltages.Turn off power to the EPP III or Generator Set 150 kW beforeassembly work.performing and installation, removal, disassembly, orWear protective gloves when performing any work on mainassemblies of the EPP III.CAUTIONLabel all cables before removing electrical or electronic assemblies orcomponents.a.Remove stanchion by PDU (1, figure 5-16).b.Open access door (2) and secure with prop (3).c. Install stanchion.RECTIFIER V5a.Refer to paragraph 5.17 and remove rubber flap and connection panel.b.Record labeling and position of cables 116, 117, and 118 from contactor K3 and remove cables.Refer to paragraph 5.10.c.Record labeling and position of cables of rectifier V5 (7), loosen screw and remove cables.d. Remove two screws (4), serrated lock washers (5), washers (6) and rectifier V5 (7). Tag andremove cables from rectifier V5 (7).5-44