2.8 PREPARATION FOR MOVEMENT.
2.8.1 Generator Set 150 kW Shutdown.
Open Flap (1, figure 2-25).
NOTE
The MASTER SWITCH (4) is a five position switch:
Position One -
Locked and Gen Set 150 kW will not run in this position.
Position Two -
Off with the key fully inserted (pushed in); Gen Set 150
kW will run in this position but cannot be started.
Position Three -
Off with the key in the half-way inserted position; this is
the NORMAL shut down position.
Position Four -
Switch is on with key fully inserted, this is the
NORMAL start and run position.
Position Five -
Switch is on with key inserted half way; this is the EMER-
GENCY shut down position.
2.8.1.1 Normal Shutdown.
a.
Press AC CIRCUIT INTERRUPTER OFF pushbutton switch (3):
AC CIRCUIT INTERRUPTER ON lamp (2) goes out.
CAUTION
Before shutting down Generator Set 150 kW, allow it to operate
for five minutes with no load applied.
b.
Turn MASTER SWITCH (4) to OFF. Pull key 1/4 to 1/2 way out from MASTER SWITCH.
2.8.1.2 EMERGENCY Shutdown.
a.
Remove key from MASTER SWITCH (4).