TM 9-6115-669-13&P
Set EMERGENCY switch (16, figure 2-22) to On. AC CIRCUIT INTERRUPTER ON lamp (8)
must go out.
2.7.5.7 Battle Short operation.
This function is utilized, in certain phases of the RS/ECS radar system, on the basis of EPP III
signals in the ECS, and prevents the generator from being shut down during that phase as a result
of the faults listed below. Power delivery from the generator must be especially reliable at this time.
The generator set will not shut down even if the following malfunctions occur:
BATTERY CHARGING CONTROL
OIL PRESSURE
OIL TEMP-CYLINDER HEAD
UNDER/OVERVOLTAGE
GENERATOR OVER TEMPERATURE
The generator set will shut down if the following faults are indicated:
UNDER/OVER FREQUENCY
OVERLOAD
RESERVE POWER
CAUTION
To prevent damage to the generator, use this function manually only for
short periods. Normally Battle Short is invoked automatically on the
basis of EPP III signals in the ECS.
a.
Turn BATTLE SHORT switch (6, figure 2-22) or (17) to On.
The BATTLE SHORT lamps (6 and 12) lights up, activating the function.
b.
Switch the function off again by setting BATTLE SHORT switch (5) or (17) to Off.
2 - 5 7