2-2 GENERATOR SET INSTALLATION.
2-2.1
a.
b.
c.
2-2.2
a.
b.
c.
d.
2-2.3
a.
b.
c.
d.
e.
2-4
General.
Exhaust discharge contains deadly gases. Do not
closed areas unless exhaust discharge is property
serve this warning could result in severe personal
monoxide poisoning.
Ensure that installation site is as level as possible.
operate generator sets in en-
vented outside. Failure to ob-
injury or death due to carbon
Provide adequate ventilation to prevent recirculation of hot air exhausted from generator set.
Refer to FIGURE 2-1 for base mounting measurements.
Outdoor Installation.
Make use of natural protective barriers.
Allow space on all sides for service and maintenance. Refer to FIGURE 2-2 for minimum clearance measure-
ments.
Ensure that site soil is firm and well drained.
Use planks or other material for support in areas where soil
Indoor lnstallation.
Exhaust discharge contains deadly gases. Do not
closed areas unless exhaust discharge is property
serve this warning could result in severe personal
monoxide poisoning.
will not support the generator set.
operate generator sets in en-
vented outside. Failure to ob-
injury or death due to carbon
Never position generator set with the air inlets near a wall or other object that in-
terferes with cooling air circulation, damage to equipment could occur.
Provide ducts and vents to outside of building if good supply of cooling air is not available.
Make air intake and outlet openings in building same size or larger as those on the generator set.
Install a gas tight metal pipe from exhaust pipe of generator set to outside of building.
NOTE
Make exhaust pipe extension as short and straight as possible with only one 90 degree
bend, if needed.
Ensure that inside diameter of exhaust pipe extension is as large or larger than generator exhaust pipe.
Hot exhaust gases can ignite flammable materials. Failure to observe this warning
could result in severe personal injury or death.
Provide for harmless discharge of hot gases and sparks. Do not direct exhaust into area containing flammable
materials.