ARMY TM 9-6115-645-24
AIR FORCE TO 35C2-3-444-12
MARINE CORPS TM 09244A/09245A-24/2
2-48.3
a.
b.
c.
d.
e.
f.
g.
2-48.4
a.
b.
c.
d.
e.
Removal.
Shut off generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Remove GROUND FAULT CIRCUIT INTERRUPTER, paragraph 2-47.3. (Do not disconnect electrical leads).
Disconnect multi-pin connector at rear of malfunction indicator panel (27, FIGURE 2-14).
Remove bolts (24), washers (25), and nuts (26).
Remove malfunction indicator panel (27) from control panel.
Installation.
Install malfunction indicator panel (27, FIGURE 2-14) in control panel with bolts (24), washers (25), and nuts (26).
Install multi-pin connector at rear of panel.
Install GROUND FAULT CIRCUIT INTERRUPTER, paragraph, 2-47.4.
Raise and secure control panel.
Connect negative battery cable. Close battery access door.
2-49 BATTERY CHARGER FUSE.
2-49.1
a.
b.
c.
d.
e.
f.
2-49.2
a.
b.
c.
d.
2-49.3
a.
b.
c.
d.
e.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Remove cap (28, FIGURE 2-14) and fuse (29) from fuse holder (32).
Tag and unsolder electrical leads from fuse holder (32).
Remove nut (30), Iockwasher (31), and fuse holder (32).
Inspection.
Shut down generator set.
Inspect for blown fuse.
Inspect fuse, fuse holder, and cap for cracks, corrosion, and obvious damage.
Replace defective parts.
Installation.
Install fuse holder (32, FIGURE 2-14) and secure with Iockwasher (31) and nut (30).
Solder electrical leads to fuse holder (32) and remove tags.
Install fuse (29) and cap (28).
Raise and secure control panel.
Connect negative battery cable. Close battery access door.
2 - 7 9