ARMY TM 9-6115-645-24
AIR FORCE TO 35C2-3-444-12
MARINE CORPS TM 09244A/09245A-24/2
2-46 CONVENIENCE RECEPTACLE.
2-46.1
a.
b.
c.
d.
2-46.2
a.
b.
c.
d.
e.
f.
g.
2-46.3
a.
b.
c.
d.
e.
f.
g.
2-46.4
a.
b.
c.
d.
e.
Inspection.
Shut down generator set.
Inspect CONVENIENCE RECEPTACLE for cracks, breaks, corrosion, bent terminals, or other indications of
damage.
Inspect cover for cracks, corrosion, or damaged springs.
Replace defective parts.
Testing.
Shut down generator set.
Remove control box top panel, paragraph 2-15.1.
Tag and disconnect CONVENIENCE RECEPTACLE (20, FIGURE 2-14) electrical leads.
Set multimeter for ohms and check for continuity between upper side terminals and Iower side terminals of each
plug outlet.
Replace CONVENIENCE RECEPTACLE if continuity is indicated between terminals.
Connect electrical leads to receptacle (20) and remove tags.
Install control box top panel, paragraph 2-15.4.
Removal.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2-15.1.
Remove screws (15, FIGURE 2-14) and nuts (16).
Remove CONVENIENCE RECEPTACLE cover (17).
Remove machine screws (18), nuts (19), and CONVENIENCE RECEPTACLE (20).
Tag and disconnect CONVENIENCE RECEPTACLE (20) electrical leads.
Installation.
Connect electrical leads to CONVENIENCE RECEPTACLE (20, FIGURE 2-14) and remove tags.
Install CONVENIENCE RECEPTACLE (20) into panel cutout with machine screws (18) and nuts (19).
Install CONVENIENCE RECEPTACLE cover (17) with screws (15) and nuts (16).
Install control box top panel, paragraph 2-15.4.
Connect negative battery cable. Close battery access door.
2-77