4-3
h.
i .
j.
k.
l.
m.
n.
o.
p.
ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
With multimeter set on OHMS, check across terminals 9 and 10. Slowly increase output voltage of G1. When
voltage reaches 23.9 +/-1.4 VAC the relay should trip. When relay trips, circuit 9 and 10 should close and circuit
11 and 12 should open.
Return output voltage of G1 to 0 and open S1 allowing relay to reset.
Place switch S2 in B position and close switch S1.
Repeat steps f. through i.
Place switch S2 in C position and close switch S1.
Repeat steps f. through i.
The voltages at which relay trips in positions A. B, and C should be within 1 volt.
Replace any relay found to be defective.
Install relay, paragraph 2-56-4.
FIGURE 4-1. Test Circuit
GOVERNOR CONTROL UNIT.
High voltage is produced when this generator set is in operation. Improper operation
could result in personal injury or death.
4-3-1 Troubleshooting Procedures
a. While holding the Master Switch (S-1) in the START position, check for the voltage from pin positions 1,3,5
on the GCU (A-5) to Ground. The readings should be battery voltage. If there is no voltage between any of the
connections, the GCU (A-5) is not receiving the proper voltage and the wiring harness should be checked. Refer
to FO-1.
NOTE
With the generator running the voltage will read zero.
4-5
