ARMY TM 9-6115-643-24
AIR FORCE TO 35C2-3-445-22
2.19.2. Removal.
a.
b.
c.
d.
e.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box top panel, paragraph 2.15.1.
Open output box access door and disconnect two control box harness connectors.
Remove bolts (1 and 5, FIGURE 2-10), Iockwashers (2), flatwashers (3), nuts (4), and control box assembly (6)
from generator set.
2.19.3. R e p a ir
Repair control box assembly by replacing damaged terminals, damaged or missing hardware, and damaged or
defective components.
2.19.4.
Installation.
a.
b.
c.
d.
2.20.
Install control box assembly (6, FIGURE 2-10) on generator set with bolts (1) and (5), flatwashers (3), Iockwashers
(2), and nuts (4).
Connect two control box harness connectors.
Install control box top panel, paragraph 2.15.4.
Connect negative battery cable. Close battery access door.
PANEL LIGHTS.
2.20.1. Inspection.
Inspect panel light holder and directional cap for cracks, corrosion, stripped threads, and other damage.
2.20.2.
Removal.
a.
b.
c.
d.
e.
f.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Release control panel by turning two fasteners and lower control panel slowly.
Tag and disconnect panel light (1, FIGURE 211 ) electrical leads.
Remove nut (2) and washer (3).
Remove panel light (1) from control panel
2.20.3.
Disassembly.
a. Remove panel light directional cap (4, FIGURE 211 ) from panel light housing (1).
b. Remove panel light bulb (5).
2.20.4. Assembly.
a. Install panel light bulb (5, FIGURE 211) into panel light housing (1).
b. Install panel light directional cap (4).
2-48