W A R N I N G
Do not operate generator set in an enclosed area unless exhaust fumes
are piped outside the enclosure. Exhaust gases contain noxious and
deadly fumes. Failure to observe this warning could result in severe per-
sonal injury or death.
C A U T I ON
Never position generator set with the air inlets near a wall or other object
that interferes with cooling air circulation, damage to equipment could
occur.
a. Provide ducts and vents to outside of building if good suppLy of cooling air is not available.
b. Make air intake and outlet openings in building same size or larger as those on the generator set.
c. Install a gas tight metal pipe from exhaust pipe of generator set to outside of building.
N O T E
Make exhaust pipe extension as short and straight as possible with only
one 90 degree bend, if needed.