ARMY TM 9-6115-643-24
AIR FORCE TO 35C2-3-445-22
4.1.2
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
n.
o.
4.1.3
a.
b.
c.
d.
e.
f.
g.
h.
i.
4-2
Testing. (Regulator. PIN: 19870 For MEP-804A Generator Set).
Shut down generator set.
Open output box access door.
Note position of voltage reconnection terminal board and set FREQUENCY SELECT switch to 60 Hz position.
Start generator set and turn VOLTAGE adjust potentiometer to ensure the adjustment ranges on TABLE 4-1 are
met, depending on position of voltage reconnection terminal board.
Shut down generator set.
If no voltage or Iow voltage was indicated, or voltage adjustment range could not be achieved, perform the following
steps. Otherwise, AC voltage regulator (2, FIGURE 4-1) is serviceable.
Disconnect wire 141 A from terminal 1 of AC voltage regulator.
Set multimeterfor DC volts and connect positive Iead to wire 141A. Connect negative lead of multimeter to terminal
3 of AC voltage regulator. Start generator set and operate at rated frequency. Move and hold MASTER SWITCH
in START position. Multi meter should indicate between 4 and 12 VDC.
Shut down generator set. Isolate wire 141A.
Set multimeter for AC volts and connect to terminals 10 and 11 of AC voltage regulator. Start generator set and
operate at rated frequency. Move and hold MASTER SWITCH in START position. Multimeter should indicate 110
to 160 VAC.
Shut down generator set.
Disconnect wire 137A from terminal 5 of AC voltage regulator. Set multimeter for ohms and connect positive lead
to wire 137A and negative lead to terminal 4 of AC voltage regulator. Move VOLTAGE adjust potentiometer to full
counterclockwise position. Multimeter should indicate no more than 2 ohms with FREQUENCY SELECT switch
in 60 Hz position or 50 Hz position. Move VOLTAGE adjust potentiometer clockwise slowly while observing multi-
meter. Multimeter should increase smoothly to approximately 20,000 ohms.
If steps h, j, and I are as indicated above, AC voltage regulator is defective and must be replaced.
Connect all wires previously disconnected.
Close output box access door.
Testing. (Reaulator. P/N: 19890-001 ForMEP-814A Generator Set).
Shut down generator set.
Open output box access door.
Note position of voltage reconnection terminal board.
Start generator set and turn VOLTAGE adjust potentiometer to ensure the adjustment ranges on TABLE 4-2 are
met, depending on position of voltage reconnection terminal board.
Shut down generator set.
If no voltage or Iow voltage was indicated, or voltage adjustment range could not be achieved, perform the following
steps. Otherwise, AC voltage regulator (2, FIGURE 4-1) is serviceable.
Disconnect wire 141 A from terminal 1 of AC voltage regulator.
Set multimeter for DC volts and connect positive Iead to wire 141A. Connect negative lead of multimeter to terminal
3 of AC voltage regulator. Start generator set and operate at rated frequency. Move and hold MASTER SWITCH
in START position. Multimeter should indicate between 4 and 12 VDC.
Shut down generator set. Isolate wire 141A.