ARMY TM 9-6115-643-24
AIR FORCE TO 35C2-3-445-22
2.71.2.
Removal.
a. Shut down generator set.
b. Open left side engine access door.
c. Unscrew air restriction indicator (1, FIGURE 221) from air cleaner housing (7).
2.71.3. Installation.
a. Install air restriction indicator (1, FIGURE 221) on air cleaner housing (7). Tighten hand tight only.
b. Close left side engine access door.
2.72. AIR CLEANER ASSEMBLY.
2.72.1.
Inspection
a.
b.
c.
d.
e.
f.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box assembly, paragraph 2.19.2.
Inspect air cleaner assembly and mounting bracket for cracks, dents, and other damage.
Install control box assembly, paragraph 2.19.4.
Connect negative battery cable. Close battery access door.
2.72.2.
Service.
a. Remove air cleaner element, paragraph 2.73.1.
b. Wipe inside of air cleaner housing with cleaning cloth (Item 7, Appendix C).
c. Install new air cleaner element, paragraph 2.73.3.
2.72.3.
Removal.
a.
b.
c.
d.
e.
f.
g.
Shut down generator set.
Open battery access door and disconnect negative battery cable.
Remove control box assembly, paragraph 2.19.2.
Loosen clamp (2, FIGURE 2-21) and remove hose (18) from air cleaner housing (7).
Remove bolts (3), washers (4), Iockwashers (5), nuts (6), mounting bracket (12), and air cleaner assembly from
generator set,
Remove bolts (8), washers (9), nuts (10), Iockwashers (11), and mounting bracket (12) from air cleaner assembly.
If replacing air cleaner, remove and retain clamps (13).
2.72.4.
Installation.
a.
b.
c.
d.
If removed, install clamps(13, FIGURE 2-21) on air cleaner housing (7).
Install mounting bracket (12) on air cleaner assembly with bolts (8), washers (9), Iockwashers(11), and nuts (10).
Install air cleaner assembly and mounting bracket (12) on generator set with bolts (3), washers (4), Iockwashers
(5), and nuts (6).
Install hose (18) and clamp (2) on air cleaner housing (7). Tighten clamp (2).
2-107