ARMY TM 9-6115-642-24
AIR FORCE TO 35C2-3-455-12
MARINE CORPS TM 09247A/09248A-24/2
2-23.4. Installation.
a.
Install GROUND FAULT CIRCUIT INTERRUPTER (8, FIGURE 2-11) in malfunction indicator panel
(12) with screws (6) and nuts (7).
b
Connect electrical leads, remove tags.
c.
Connect negative battery cable and close access door.
2-24. MALFUNCTION INDICATOR PANEL.
2-24.1
a.
b.
c.
d.
2-24.2
a.
b.
2-24.3
a.
b.
c.
d.
e.
f.
2-24.4.
a.
b.
c.
d.
e.
f.
inspection.
Shut down generator set.
Release control panel by turning two fasteners and lower control panel slowly.
Inspect malfuction indicator panel for cracked housing, loose mounting, corrosion, and other damage.
Raise and secure control panel.
Testing.
Depress TEST/RESET button and check that all indicators are lit.
Replace malfunction indicator panel if one or more indicators do not light.
Removal.
Shut down generator set.
Open left side engine access door and disconnect negative battery cable.
Release control panel by turning two fastners and lower control panel slowly.
Remove GROUND FAULT CIRCUIT INTERRUPTER, paragraph 2-23.3.
Disconnect multi-pin connector (13, FIGURE 2-11) at rear of malfunction indicator panel (12).
Remove screws (9), washers (10), nuts (11), and malfunction indicator panel (12) from control box.
Installation.
Install malfunction indicator panel (12, FIGURE 2-11) in control box assembly.
Install bolts (9), washers (10), and nuts (11).
Install multi-pin connector (13) at rear of panel.
Install GROUND FAULT CIRCUIT INTERRUPTER, paragraph 2-23.4.
Raise and secure control panel.
Connect negative battery cable and close access door.
2-25. BATTERY CHARGING FUSE ASSEMBLY.
2-25.1. Inspection.
a. Shut down generator set.
b.
Release control panel by turning two fasteners and lower control panel slowly.
c.
Inspect for blown fuse.
d.
Inspect fuse, fuse holder, and cap for cracks, corrosion, and obvious damage.
e. Replace defective parts.
f.
Raise and secure control panel.
Change 4 2-50.1/(2-50.2 blank)