ARMY TM 9-6115-642-24
AIR FORCE TO 35C2-3-455-12
MARINE CORPS TM 09247A/09248A-24/2
2-28.4. Removal.
a.
Shut down generator set
b.
Open left side engine access door and disconnect negative battery cable.
c.
Remove control box top panel, paragraph 2-16.1.
d.
Tag and remove frequency transducer (24, FIGURE 2-11) electrical leads.
e.
Open load terminal board access door and remove screws (22), nuts (23), cable clamp (48), and
frequency transducer (24).
2-28.5. Installation.
a.
Install frequency transducer (24, FIGURE 2-11) with screws (22), and nuts (23)
b.
Connect electrical leads and remove tags
c
Install control box top panel, paragraph 2-16.4
d.
Connect negative battery cable. Close access doors
2-29. SHUNT.
2-29.1 Inspection.
a
Shut down generator set.
b
Release control panel by turning two fasteners and lower control panel slowly.
c
Inspect shunt for cracks, burned or broken terminals, corrosion, and other damage
d
Raise and secure control panel.
2-29.2. Testing.
a.
Shut down generator set.
b
Open left side engine access door and disconnect negative battery cable
c.
Release control panel by turning two fasteners and slowly lower control panel.
d
Tag and disconnect shunt (27, FIGURE 2-11) electrical leads.
e.
Set multimeter for ohms and connect to shunt terminals 1 and 4. Multimeter should indicate less than
0.5 ohms.
f.
Replace shunt if multimeter indication is greater than above.
g.
If no repair is needed, connect electrical leads to shunt (27) and remove tags
h
Connect negative battery cable. Close access door.
I.
Raise and secure control panel
2-29.3. Removal.
a.
Shut down generator set
b.
Open left side engine access door and disconnect negative battery cable.
c
Release control panel by turning two fasteners and lower control panel slowly.
d
Tag and disconnect shunt (27, FIGURE 2-11) electrical leads.
e
Open storage box access door to gain access to remove screws (25), nuts (26), and shunt (27)
2-29.4. Installation.
a.
Install shunt (27, FIGURE 2-11) with screws (25) and nuts (26)
b.
Connect electrical leads and remove tags
c.
Raise and secure control panel
d.
Connect negative battery cable. Close access doors
Change 4 2-55