TABLE 3-1. Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Engine fails to crank.
Step 1.
Check that DEAD CRANK switch is in the NORMAL position.
Plain switch in NORMAL position.
Step 2.
Check that DC CONTROL POWER circuit breaker is energized (in).
If DC CONTROL POWER circuit breaker is deenergized (out), go to Step 3.
Step 3.
Check that Emergency Stop Switch is out.
Step 4.
Defect is Engine Starting/Electrical System.
Check battery connections. If loose or corroded, notify next higher maintenance level.
2.
Engine cranks but fails to start.
Step 1.
Cold ambient temperature.
If ambient temperature is below 40°F (4°C) turn MASTER SWITCH to PREHEAT position for a
maximum of 30 seconds prior to cranking engine, refer to paragraph 2-10.1.
Step 2.
Check for dirty air cleaner element.
Service air cleaner assembly, refer to paragraph 3-3.3.2.
Step 3.
Check for dirty fuel filter/water separator.
Service fuel filter/water separator, refer to paragraph 3-3.6.2. If engine still fails to start, notify next
higher maintenance level.
3.
Engine starts but stops when MASTER SWITCH is released from START position.
Step 1.
Check for proper starting procedure.
Hold MASTER SWITCH in START position until 25 psi (172 kPa) is reached, refer to paragraph 2-10.1.