ARMY TM 9-6115-642-10
AIR FORCE TO 35C2-3-455-11
MARINE CORPS TM 09247A/09248A-10/1
2-19
2-19.1 General. The NATO slave receptacle can be used to
start the generator set when batteries are discharged.
2-19.2
a. Connect one end of NATO slave cable to fully charged
24 VDC system and other end to discharged generator
sets NATO slave receptacle. Start discharged
generator set.
b. Refer to Paragraph 2-10.
c. Remove NATO slave cable after generator set starts.
2-20
2-20.1 General. Depressing the EMERGENCY STOP
pushbutton will stop the generator set.
NOTE
The generator set cannot be restarted without
resetting the EMERGENCY STOP pushbutton
and turning MASTER SWITCH to OFF position.
2-21
Continued operation using the BATTLE SHORT
switch can result in damage to the generator set.
NOTE
If any emergency situation requires continued
operation of the generator set, the BATTLE
SHORT switch is used to override all the safety
devices except the short circuit devices, and
EMERGENCY STOP function.
NOTE
BATTLE SHORT switch must be OFF to start
generator set.
a. Start generator set if set is not running. Refer to
paragraph 2-10.
b. Lift cover on BATTLE SHORT switch and position
switch to ON.
2-34 Change 1