TM 5-6115-630-14&P
Item
no.
20
Table 3-2. Operator/Crew Preventive Maintenance Checks and Services (PMCS) (cont).
B Before
D During
A After
W Weekly
B
Interval
D
A
w
M
Item to be inspected.
Procedure: check for and have repaired,
filled, or adjusted as needed
GENERATOR SET GAGES AND
INSTRUMENTS (cont)
d.
e.
Check that voltmeter (22) indicates desired
output voltage as determined by load connec-
tions and amps-volts transfer switch.
4874-013
Check engine oil pressure gage (23) for 25 psi
indication.
M Monthly
Equipment is not
ready/available if:
Desired voltage cannot be
obtained and maintained.
Oil pressure drops below
15 psi.
3-13