TM 5-6115-629-14&P(5) Position beveled washers (6) so that screw heads are parallel to tops of washers. Whileholding beveled washers in position, tighten hardware.(6) Connect generator set ground wire (1) to trailer GROUND TERMINAL stud (3).Section IV. MAINTENANCE OF ELECTRICAL SYSTEM5-6. Power Cable Repair. The power plant cables are repaired by resoldering or replacing loose ordamaged contacts inside the connector. A soldered contact can be unsoldered and a new one in-stalled in its place. If, however, the damaged contact is crimped onto the wire, or if the wire is brok-en, the contact must be cut off. When one wire in the cable has been cut or broken, all wires must becut to the same length and new contacts soldered on each. Refer to TB SIG 222 (TO 31-3-64) andTM 55-1500-323-25 (TO 1-1A -14).a. Removal.NOTECable grip nut is left hand threaded. Turn clockwise to loosen.(1) Unscrew cable grip nut (1, figure 5-5) from housing (2).(2) Slide cable grip nut (1), packing gland (3) and collar (4) up cable (5) away fromhousing (2).(3) Remove three screws (6) and three washers (7) and separate housing (2) from plugshell (8).(4) Remove spacer (9) and insert (10) from plug shell (8).(5) Remove contact(s) (11) being repaired or replaced from spacer (9) and insert (10).Unsolder contact(s) (11) from wire(s) (12).NOTEIf contact is crimped onto wire, or if wire is broken, do steps (6) through (8).(6) Cut contacts (11) off wires (12).(7) Strip back cable jacket to expose more of individual wires.(8) Cut wires to equal length. Strip and tin wires in accordance with procedures given intechnical manuals referenced above.5-5