4-4
TM 5-6115-629-14&P
NOTE
When performing step 10, note that the power cables, the individual wires in
the cables, and the generator set load terminals are all marked for
identification. Make certain these markings correspond when connecting
power cables.
(10) Connect power cable to each generator set load terminal board as follows:
(a) White wire to load terminal L0.
(b) Black wire to load terminal L1.
(c) Red wire to load terminal L2.
(d) Blue wire to load terminal L3.
(11)
(12)
(13)
(14)
Connect both power cables to switch box.
WARNING
Do not operate power plant until both power units have been properly grounded
(paragraph 4-2, b.) Serious injury or death by electrocution can result from
operating an ungrounded power plant.
CAUTION
To avoid damage to equipment, make certain of voltage, frequency,
phase requirements of load being connected to power plant.
and
Connect power plant switch box to system or equipment to be powered. Refer to
TM 5-6115-545-12 and generator set load terminal board data plate. Data plate is located
on inside of generator enclosure door nearest load terminals.
Remove quick-release pins securing both power unit personnel platforms and lower
platforms.
On both power units, open control panel doors and the two doors immediately below
control panels.
the