(2) Set both switches on switch box to OFF position.
(3) Start one power plant generator set and bring generator up to rated speed, voltage, and frequency.
(4) Set generator set circuit breaker to ON position.
(5) Set associated switch on switch box to ON position.
NOTE
When the power plant generator set in operation must be shut down, follow steps (6) thru
(10) to continue to supply power to system or equipment being powered.
(6) Start second power plant generator set and bring up to rated speed, voltage, and frequency.
(7) Set generator circuit breaker to ON position.
(8) At switch box, set switch associated with first generator set to OFF position.
(9) Set switch box switch associated with second generator set to ON position.
(10) Shut down first power plant generator set.